Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.1 Examination and Maintenance No No Cylinder is damaged and no longer able hold a seal around the packing 6/10/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No provide operational telephone 12/9/2025
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No ceiling panels removed and smoke detector covered 9/26/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) No No 1.6 telephone does not work 9/26/2019
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No non elevator items stored in machine room 12/17/2019
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No ceiling panels in machine room need replaced 12/17/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No interior panels need replaced to prevent bulb breakage 12/17/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No telephone does not work disconnected 10/22/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No needs current certificate posted 12/17/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No B(11)/1.6.1 : Alarm bell shall work with power loss. (REINSPECTION REQUIRED) 10/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No G/8.6.5.5.2 Pit scavenger pump will be removed or routed to a measurable container. 10/31/2023
MO Minimum : Elevators (I) - Pits (I)1 No No I(1)/106.1 Pit shall be kept free of excessive debris. 10/31/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No B(11)/1.6.1 : Alarm bell shall work with power loss. (REINSPECTION REQUIRED) 10/5/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Door operator belts cracked/dry rotted. Replace all. 1/1/2022
MO Minimum : Elevators (I) - Pits (I)1 No No I(1)/106.1 Pit shall be kept free of excessive debris.(2020 and 2021) 1/1/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No B(11)/1.6.1/ : 2-way communication device shall work and give proper location (REINSPECTION 15days) 9/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light & alarm bell - needs new battery. Re-inspection required 7/27/2023
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Remove all non elevator related items from machine room 10/31/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display current operating certificate in machine room 10/31/2023
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Provide phase one instructions at main level hall station 10/31/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Provide operational telephone inside elevator cab 8/27/2024