Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits water in pit rusting springs and channels 12/17/2019
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate needs current certificate posted on site 12/17/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits pit light not working 12/17/2019
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept dry. 4” water in Pit, drain, remove rust from pit channels, repaint, repair water leak. (2020 & 2021 violation) 10/15/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements G(1) CARTOP: Clean/remove debris and metal dust covers 10/15/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements G(1) Adjust all upthrust roller bearings for proper clearance, currently as much as 0.125”. 10/15/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Machine Room Fire Extinguisher shall have current monthly/annual test tag. Expired 10/15/2024
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lighting needs to be repaired 10/15/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing and self-locking (currently deadbolt, not self locking) 10/15/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 I(1)/106.1 Pit shall be kept dry. Remove rust from pit channels, repaint, repair water leak. 8" water in pit 10/15/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display current operating certificate in machine room 10/24/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Provide current state operating certificate in machine room 8/27/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x G(1)Emergency/auxiliary lighting shall work with power loss. (2020 & 2021 VIO) 9/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Car Door restrictor shall work. 9/7/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 x Machine room door needs to be self closing & self locking. Re-inspection required 7/27/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x G(1)/8.6.4.15/1.5.1(b) : Emergency lighting shall work with power loss. (Reinspection required) 10/5/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x telephone needs to be replaced 10/22/2019