Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (I) - Pits | (I)1 | The elevator pit is full of water. The water shall be removed and the sump pump shall be made operational | |||
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | x | 1. Car door restrictor does not work. Repair. Rule G-1, Missouri minimum. Rule 8.11.3.1.1(R) A17.1, 2016. Rule 1.18, A17. 2, 2014Reinspect by 3-28-22(30 days) | 4/8/2022 | |
MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x | Emergency alarm does not work on battery power | 5/3/2023 |