Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x 1. Car door restrictor does not work. Repair. Rule G-1, Missouri minimum. Rule 8.11.3.1.1(R) A17.1, 2016. Rule 1.18, A17. 2, 2014Reinspect by 3-28-22(30 days) 4/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency alarm does not work on battery power 5/3/2023
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit is full of water. The water shall be removed and the sump pump shall be made operational