Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No The machine room shall have permanent lighting of not less than 10 fc.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The machine room shall be enclosed and accessible only to authorized personnel.
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No The lighting in the stairway going up to the machine room shall be operational.
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Provide a current tested ABC fire extinguisher in the machine room.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No The machine room shall have permanent lighting of not less than 10 fc.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The machine room shall be enclosed and accessible only to authorized personnel.
MO Minimum : Elevators (H) - Machine Rooms (H)1 No No The lighting in the stairway going up to the machine room shall be operational.
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Materials not necessary for the maintenance or operation of the elevator shall not be stored in the machine room.
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Provide a current tested ABC fire extinguisher in the machine room.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No Yes The cab lighting shall be operational and not less then 5fc. Elevator Red Tagged due to alarm bell and cab lighting both not working. There is no phone or intercom. 6/5/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes Yes The alarm bell shall be operational. Elevator Red Tagged due to alarm bell and cab lighting both not working. There is no phone or intercom. 6/5/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Car gate and hoistway doors, as well as governor pullout/pullthru, and governor switch and jaw were the only tests witnessed on 2/21/2020. All other tests required by MO CSR 40-5.090 have yet to be performed and shall be rescheduled to complete category 5 test and periodic inspection. Other deficiencies may be noted after testing is complete. 1/25/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Car gate and hoistway doors, as well as governor pullout/pullthru, and governor switch and jaw were the only tests witnessed on 2/21/2020. All other tests required by MO CSR 40-5.090 have yet to be performed and shall be rescheduled. Other deficiencies may be noted after testing is complete. 6/5/2020