A17.1-2016 : Elevators
|
4.5 - Access to Hoistway
|
2.12.7
|
x
|
|
2.12.7.3.3(3)(d) Access Key Switch @ top landing non functional must correct issue and reinspect.
|
8/26/2024
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.1 Phase I Emergency Recall Operation
|
x
|
x
|
2.27.3.1.1(a) (b)(c) With the MOD Fixture Change the Phase I Key Switch had not been changed so the Key Operation could not be verified.
|
8/26/2024
|
A17.1-2016 : Elevators
|
1.18 - Restricted opening of car or hoistway doors
|
2.14.5.7
|
x
|
|
Car door restrictor must be adjusted electrical must open prior to the mechanical which is set at 4 inches.
|
8/26/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency lights not working
|
2/2/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Need "In Case Of Fire" signs
|
1/29/2024
|