Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Fire extinguisher needs to be serviced. 3/29/2019
conversion conversion n/a Machine room door should be locked at all times. 6/28/2018
conversion conversion n/a Machine room shall not be used as a storage locker. Clean out items not associated with elevator operation. 6/28/2018
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean & dry 4/10/2024
MO Minimum : Elevators (I) - Pits (I)8 Sump pump needs cover. 3/29/2019
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit floor is covered in water. The elevator pit shall be kept clean and dry
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) The pit light fixture failed to illuminate in the pit. Repair pit light fixtures to provide lighting of not less than five (5) foot candles at the pit floor for maintenance and emergency personnel.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection There is a oil recovery unit installed in the pit of this elevator designed to return the oil leakage from the packing gland on the cylinder head. The State of Missouri has determined that this device does not suffice for oil leakage and is only allowed for temporary use until the packing gland can be repaired/replaced. Remove the recovery unit after the packing gland has been repaired/replaced and record the oil loss per A17.1 2016 - 8.6.5.5.7