ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
ememgency phone inoperative
|
8/15/2022
|
|
A17.1-2016 : Elevators
|
1.7 - Car door or gate
|
8.6.4.13.1 Door Systems General
|
x
|
|
Manual Car gate (collapsible) needs a door handle to prevent pinch hazard
|
1/20/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.1.1
|
|
|
Machine room door shall be self-locking.
|
11/9/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Required documentation & MCP shall be kept in equipment room including wiring diagrams, oil log, and fire service log recorded monthly.
|
11/9/2025
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
8.7.2.1.1 Hoistway Enclosure Walls
|
x
|
|
Hoistway needs fire proofing near floors, 1, 4, and 5
|
1/20/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4 Access to Pit
|
x
|
|
Walk in pit door shall have safety switch installed.
|
2/19/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.4 Access to Pit
|
|
|
Walk in pit door shall have safety switch.
|
11/9/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.11.2.2.6 Fire Fighters Operation (Re-Inspection)
|
x
|
|
Fire service operation shall be tested.
|
5/2/2025
|
|
A17.1-2016 : Elevators
|
6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators
|
2.27.3
|
x
|
x
|
FEO phase 2. Hold does not work. Stop switch in fire panel does not work.
|
1/20/2026
|