Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel x FEO Phase II, hold does not work. Shall not accept car calls while in HOLD.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Access to Pit x Walk in pit door shall have safety switch installed. 2/19/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x The in car emergency lighting shall work. 2/19/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x UNIT IS RED-TAGGED BECAUSE THE ROPE GRIPPER DID NOT WORK WHEN TESTING THE UNINTENDED MOVEMENT UP. 5/2/2025
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Reinstall covers on rope gripper. 1/14/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 The machine room door shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. 1/14/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 Machine room door shall be self locking. 1/14/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 Access to Pit Walk in pit door shall have safety switch. 1/14/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Required documentation and MCP shall be kept in equipment room including wiring diagrams, oil log, and fire service log recorded monthly. 1/14/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Reinstall covers on rope gripper. 1/14/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. 1/14/2026