Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Fire extinguisher in machine room is expired, needs serviced or replaced 12/7/2022
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 Machine room 110 supply shall be installed to the NFPA 70 with receptacle box mounted securely to the wall 12/7/2022
A17.1-1996 : Elevators 3.10 - Hoistway construction 100 Patch/repair all holes in the hoistway walls. Hole in hoistway wall about 8' to 10' looking through to the back of interior sheet rock office wall. Also, other smaller holes. 3/1/2026
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code Repair machine room lights. 5/12/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/1/2026
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm bell does not work on emergency 110v power or normal power 12/30/2021
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 1001.2(e)(10) x x Safety Operated Switch attached to governor rope is broken and not operable. RED TAG 12/30/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Inspection is incomplete, must complete all weight testing and spinning the governor. Spring buffers do not need compressed. 12/30/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Brake failed to hold capacity load. Car removed from service. 2/11/2022
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 205.11 x x Car safety wind up drum cable had 2 wraps left on the drum after setting the safeties. Repair or replace cable or safeties 3/24/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency alarm bell shall be operational. 2/21/2024
A17.1-1996 : Elevators 3.10 - Hoistway construction 100 x Holes need to be patched in hoistway. (Repeat Violation) Re-Inspection required. 4/8/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency alarm bell shall be operational. (Repeat Violation) Re-Inspection required. 4/8/2025
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency alarm bell shall be operational. (Final Notice) This violation shall be corrected immediately or the unit will be red tagged out of service until corrected. 3/1/2026
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 203 x x SOS switch shall be operational. Elevator left down/out of service. 3/1/2026