MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Inspection is incomplete, must complete all weight testing and spinning the governor. Spring buffers do not need compressed.
|
12/30/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Brake failed to hold capacity load. Car removed from service.
|
2/11/2022
|
A17.1-1996 : Elevators
|
3.10 - Hoistway construction
|
100
|
|
|
Patch/repair all holes in the hoistway walls. Hole in hoistway wall about 8' to 10' looking through to the back of interior sheet rock office wall. Also, other smaller holes.
|
|
A17.1-1996 : Elevators
|
3.10 - Hoistway construction
|
100
|
x
|
|
Holes need to be patched in hoistway. (Repeat Violation) Re-Inspection required.
|
4/8/2025
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell does not work on emergency 110v power or normal power
|
12/30/2021
|
A17.1-1996 : Elevators
|
2.3 - Lighting and receptacles
|
1001.2(b)(3) Inspection code
|
|
|
Repair machine room lights.
|
5/12/2020
|
A17.1-1996 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
1001.2(e)(10)
|
x
|
x
|
Safety Operated Switch attached to governor rope is broken and not operable. RED TAG
|
12/30/2021
|
A17.1-1996 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
102.1
|
|
|
Machine room 110 supply shall be installed to the NFPA 70 with receptacle box mounted securely to the wall
|
12/7/2022
|
A17.1-1996 : Elevators
|
2.7 - Fire Extinguisher
|
1206.1h
|
|
|
Fire extinguisher in machine room is expired, needs serviced or replaced
|
12/7/2022
|
A17.1-1996 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
203
|
x
|
x
|
SOS switch shall be operational. Elevator left down/out of service.
|
|
A17.1-1996 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
205.11
|
x
|
x
|
Car safety wind up drum cable had 2 wraps left on the drum after setting the safeties. Repair or replace cable or safeties
|
3/24/2022
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency alarm bell shall be operational.
|
2/21/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency alarm bell shall be operational. (Repeat Violation) Re-Inspection required.
|
4/8/2025
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency alarm bell shall be operational. (Final Notice) This violation shall be corrected immediately or the unit will be red tagged out of service until corrected.
|
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|