Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Alarm bell does not work on emergency 110v power or normal power 12/30/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Brake failed to hold capacity load. Car removed from service. 2/11/2022
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 205.11 x x Car safety wind up drum cable had 2 wraps left on the drum after setting the safeties. Repair or replace cable or safeties 3/24/2022
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1206.1h Fire extinguisher in machine room is expired, needs serviced or replaced 12/7/2022
A17.1-1996 : Elevators 3.10 - Hoistway construction 100 x Holes need to be patched in hoistway. (Repeat Violation) Re-Inspection required. 4/8/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Inspection is incomplete, must complete all weight testing and spinning the governor. Spring buffers do not need compressed. 12/30/2021
A17.1-1996 : Elevators 2.8 - Pipes, wiring, and ducts 102.1 Machine room 110 supply shall be installed to the NFPA 70 with receptacle box mounted securely to the wall 12/7/2022
A17.1-1996 : Elevators 3.10 - Hoistway construction 100 Patch/repair all holes in the hoistway walls. Hole in hoistway wall about 8' to 10' looking through to the back of interior sheet rock office wall. Also, other smaller holes.
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 1001.2(b)(3) Inspection code Repair machine room lights. 5/12/2020
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 1001.2(e)(10) x x Safety Operated Switch attached to governor rope is broken and not operable. RED TAG 12/30/2021
A17.1-1996 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 203 x x SOS switch shall be operational. Elevator left down/out of service.
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency alarm bell shall be operational. 2/21/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency alarm bell shall be operational. (Final Notice) This violation shall be corrected immediately or the unit will be red tagged out of service until corrected.
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency alarm bell shall be operational. (Repeat Violation) Re-Inspection required. 4/8/2025