MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current fire extinguisher shall be mounted in the machine room located convenient to the access door.
|
7/1/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
7/1/2020
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
The electrical junction box under the car platform shall be covered.
|
7/1/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-closing and self-locking.
|
7/1/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
8.6.3.2.1 - Suspension cable anti-rotation devices shall be installed.
|
7/1/2020
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)1(A)
|
|
|
Suspension rope and governor rope tags shall be installed.
|
7/1/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
6/27/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
6/27/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
|
6/27/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)16
|
|
|
The electrical box on the underside of the car shall have a cover installed.
|
6/27/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
|
|
Suspension cables shall have an anti-rotation device installed.
|
6/27/2022
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Water and oil shall not be allowed to accumulate on pit floor. The pit has about 3" of standing water in it.
|
|