|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.5 - Housekeeping
|
8.6.4.9 Cleaning of Car Tops
|
|
|
Car top needs cleaned of dirt and oil
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.2
|
x
|
|
Ropes shall be shorted to allow for proper counterweight runby.
|
|
|
conversion
|
conversion
|
n/a
|
|
|
Replace suspension ropes (Excessive rouging and reduced diameter)
|
4/28/2020
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Loud static on phone prevents two way communication
|
3/17/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.11.2.1.5(b)
|
x
|
|
When car is level at top floor there is less than 6” of Runby between counterweight and buffer
|
3/17/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
x
|
|
Replace broken springs on counterweight rope shackles
|
12/18/2023
|