Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Loud static on phone prevents two way communication 3/17/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.11.2.1.5(b) x When car is level at top floor there is less than 6” of Runby between counterweight and buffer 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts x Replace broken springs on counterweight rope shackles 12/18/2023
conversion conversion n/a Replace suspension ropes (Excessive rouging and reduced diameter) 4/28/2020