Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.5 - Housekeeping 8.6.4.9 Cleaning of Car Tops No No Car top needs cleaned of dirt and oil
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Loud static on phone prevents two way communication 3/17/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Yes No Replace broken springs on counterweight rope shackles 12/18/2023
conversion conversion n/a No No Replace suspension ropes (Excessive rouging and reduced diameter) 4/28/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.2 Yes No Ropes shall be shorted to allow for proper counterweight runby.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 8.11.2.1.5(b) Yes No When car is level at top floor there is less than 6” of Runby between counterweight and buffer 3/17/2022