Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors Yes No Car door restrictor does not work. 4/15/2021
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) Yes No Car door restrictor is not working. Re-inspection required 6/6/2025
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors Yes No Car door restrictor shall be made operable 2/22/2024
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) Yes No Car door restrictor shall be made operable. Re-inspection required 9/3/2024
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors Yes No Car door restrictor shall be made operable. Re-inspection required 2/3/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Elevator cab phone does not work, needs repaired. Re-inspection required 2/3/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Elevator cab phone does not work, needs repaired. Re-inspection required 9/3/2024
MO Minimum : Elevators (I) - Pits (I)1 No No Elevator pit shall be kept clean and dry, this elevator pit has water standing and has damaged pit equipment 8/21/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Elevators connected to an emergency generator shall be tested for operation on emergency power. Re-inspection required 9/3/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone line is not working. Re-inspection required 3/13/2023
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current operating certificate in machine room. 8/21/2025
MO Minimum : Elevators (I) - Pits (I)2 No No The pit channels are every corroded due to excessive water in the pit 8/21/2025
MO Minimum : Elevators (I) - Pits (I)2 No No The pit channels are very corroded due to excessive water in the pit 8/21/2025