| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x |  | The in car alarm bell shall be operational on auxiliary power. | 6/15/2023 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | x |  | Emergency lights do not work. | 4/15/2022 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | x |  | The in car emergency lights shall be operational. | 6/15/2023 | 
                
                    | MO Minimum : Elevators | (H) - Machine Rooms | (H)2 |  |  | The machine room gates shall be self-closing, self-locking and shall be operable from the interior space without the use of a key. | 11/30/2023 | 
                
                    | MO Minimum : Elevators | (H) - Machine Rooms | (H)2 |  |  | Sliding gate to machine room shall be self closing | 4/16/2024 | 
                
                    | MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate |  |  | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/30/2023 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records |  |  | The TKE MCP shall have all the information filled out. | 11/30/2023 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) |  |  | The MCP needs to be updated and filled out, including monthly fire service checks | 4/16/2024 | 
                
                    | MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers |  |  | Fire extinguisher in machine room is expired, replace or have serviced | 4/16/2024 | 
                
                    | MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log |  |  | A record of findings for firefighters' service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be available on-site. | 11/30/2023 |