Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)2 machroom door lock if defeatable need to change to undefeatable
A17.1-2016 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage remove hoses from cyl. heads back to tanks
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Backup light and bell inop. 1/11/2024
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x phone was answerwd but person on other end couldnt tell me where i was located. voice quility was very bad couldnt understand conversation
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x door restrictor didnt work