MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
Cover pit sump with non-combustible cover.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current operating certificate in the elevator machine room.
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)4
|
|
|
Remove all non-elevator related materials from the machine room.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
The lights inside the elevator shall have a protective cover.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
7/15/2022
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)8
|
|
|
The pit sump hole shall be covered flush with the pit floor. The covering shall consist of noncombustible material.
|
7/15/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Door close function while on fire service shall be constant pressure.
|
1/18/2024
|