Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)7 x The elevator feeder disconnect in the machine room has malfunctioned and will not disconnect power to the shunt trip disconnect. The elevator feeder disconnect shall be repaired or replaced to the latest version of NFPA 70. Reinspection is required.
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)4 The belts on the hydraulic pump motor are loose and slip tension under higher pressure. Tighten belts for a smooth operation of pump to motor.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The ventilation cooling fan in the machine room shall be repaired to provide proper operation temperature for the elevator controller with the controller doors fully closed as designed.