Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 8/14/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 (Re-Inspection) x 2.8.3.3.2 - The battery lowering device shall not be operational when the shunt trip is activated. 10/26/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided x Provide a pit sump system with an alarm system to detect oil in the water. 10/26/2020