MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
IN CAR EMERGENCY PHONE NEED TO BE PROGRAMED
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone does not operate
|
2/4/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate
|
10/11/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency phone does not operate
|
10/6/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.2 Replacement of Suspension Means (Re-Inspection)
|
x
|
|
Replace undersized and rouged hoist ropes.
|
10/4/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone does not operate
|
10/4/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
Post In Case of Fire signage next to hall button fixture at lobby landing
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
|
|
Pit light does not illuminate
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)5
|
|
|
MOVER PIT LADDER TO HOISTWAY DOOR INTERLOCK SIDE
|
|
A17.1-2016 : Elevators
|
3.23 - Suspension Means
|
8.6.3.2 (Re-Inspection)
|
x
|
|
Replace hoist ropes. Ropes are rouged and undersized
|
2/4/2025
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
8.6.4.11
|
x
|
|
Need to shorten hoist ropes. Counterweight fully compresses buffer before car actuates top final limit switch.
|
10/12/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
State operating certificate not displayed in machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate inside the machine room
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current state operating certificate inside machine room
|
|