Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work when normal power is removed. Reprogram phone to new maintenance company 7/19/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Two-way communication is not working. Re-inspection required 6/24/2025
MO Minimum : Elevators (E) - Machines (E)1 No No Low pressure switch on control valve does not work. Repair and Reinspect within 30 days. 2.37 1/3/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Remove scavenger unit from the pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Provide code compliant means to collect oil from piston in the pit.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Packing on piston needs replaced, excessive leaking
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Unit has oil recovery pump in pit. Replace with proper receptacle to measure oil leakage from jack
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Unit has oil recovery pump in pit. Replace with proper receptacle to measure oil leakage from jack
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Provide code compliant means to collect oil from the piston
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Unit has oil recovery pump in pit. Need to replace with proper receptacle to measure oil leakage from jack
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Unit has oil recovery pump in pit. Replace with proper receptacle to measure oil leakage from jack 7/19/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Packing on piston shall be replaced, excessive leaking
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No Provide current year documents for the MCP.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.1 General Maintenance Requirements Documentation No No A written maintenance control program shall be kept on site for each elevator 7/19/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Yes No Packing on piston needs replaced, excessive leaking. Re-inspection required
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Need to remove scavenger unit from pit
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light needs to be repaired. 10/9/2020
MO Minimum : Elevators (I) - Pits (I)1 No No Need to remove scavenger unit from pit
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current certificate.