Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)1 Install capacity plate in car
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 4/24/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x The in car emergency telephone shall be operational. 2/23/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 The top of car emergency exit shall only be operable from the top of the car.
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 x The top of car emergency exit shall only be operable from the top of the car. (Violation from prior inspection needs to be verified as corrected)
MO Minimum : Elevators (F) - Electrical Switches (F)1 x Car shall have emergency stop switch. 4/24/2023
MO Minimum : Elevators (F) - Electrical Switches (F)1 x Car shall have emergency stop switch. (Violation from prior inspection needs to be verified as corrected)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers x No fire extinguisher in machine room. A current tested and tagged ABC type fire extinguisher shall be provided in the machine room. Multi-year violation. Re-Inspection required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Fire service check charts are not current, Evacuation procedures and maintenance chart are missing.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency telephone shall be operational. 1/27/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lighting in the machine room shall be not less than ten (10) foot-candles at floor level.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lighting in the machine room shall be not less than ten (10) foot-candles at floor level.
MO Minimum : Elevators (H) - Machine Rooms (H)1 Service fire extingusher in machine room
MO Minimum : Elevators (H) - Machine Rooms (H)2 Machine room door shall be self-closing and self-locking.
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lighting shall be not less than 10 foot-candles at the floor.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) A permanent lighting fixture shall be provided in all pits to provide an illumination of not less than five (5) foot-candles at the pit floor.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit shall have code compliant lighting.
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. Clean the pit.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) A permanent lighting fixture shall be provided in all pits to provide an illumination of not less than five (5) foot-candles at the pit floor.
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean and dry. The pit shall be cleaned.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) x The pit light switch shall be accessible from the pit door and code compliant pit lighting shall be provided. Multi-year violation. Re-Inspection required.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The elevator broke down in the middle of the annual inspection and category 5 test. All category 5 testing items still remain and shall be witnessed. 1/27/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state certificate in machine room