MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A copy of the MCP shall be kept in the machine room for each elevator
|
9/28/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light in car shall work. Re-inspection required
|
9/27/2022
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
|
In car emergency stop switch shall work. Re-inspection required
|
9/27/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
x
|
|
In car Fire service Phase I recall light shall work. Re-inspection required
|
9/27/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
x
|
|
Car gate reversing edge shall work. Re-inspection required
|
9/27/2022
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Adjust hoistway door gap at second floor when car is away from floor
|
9/28/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Car failed 15 minute stand test, tech determined that it was back flowing through the valve.
|
4/17/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Numerous parts of Phase II operations failed.
|
4/17/2023
|