MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A copy of the MCP shall be kept in the machine room for each elevator
|
5/22/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace broken door close button in car operating panel
|
9/24/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Provide testing of Phase I operations,record results.
|
5/24/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Provide testing of Phase II operations, record results.
|
5/24/2023
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Emergency light inoperative. Repair
|
2/26/2020
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light inoperative.
|
10/12/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm bell inoperative.
|
10/12/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Alarm bell does not work.
|
2/26/2020
|
A17.1-1996 : Elevators
|
3.2 - Car top light and outlet
|
204.7
|
|
|
Repair non-working cartop light
|
9/24/2024
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Alarm Bell and emergency light inoperative repair
|
4/24/2019
|
conversion
|
conversion
|
n/a
|
|
|
Tank to jack supply line needs additional support inside equipment room near tank
|
4/24/2019
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
5/24/2023
|