MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency light and bell are inoperative. Repair.
|
8/27/2019
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A copy of the MCP shall be kept in the machine room for each elevator
|
5/22/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Fire fighters Phase I instruction sign at key switch is not legible. Replace sign
|
5/22/2023
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)3
|
|
|
Hoistway doors at middle landing shall be adjusted to reduce gap between doors when closed and locked
|
5/22/2023
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)1
|
|
|
Remove mounted fire extinguisher from inside the elevator. See ‘96 204.3a
|
5/19/2023
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)6
|
|
|
Post missing signs in car as needed. No pass., class freight.
|
5/19/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace missing cotter pin on car door rod(s) as needed.
|
5/19/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean the pit.
|
5/19/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace missing controller cooling fan.
|
5/19/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Provide existing emergency lights and bell to work.
|
5/12/2023
|
MO Minimum : Elevators
|
(C) - Car Enclosure: Freight
|
(C)6
|
|
|
Provide Loading class" sign in car enclosure.
|
9/24/2024
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned
|
9/24/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Gate to machine space needs to be self locking
|
9/24/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Pipes over elevator controllers and disconnect switches need to be guttered to prevent and possible leakage from getting into electrical equipment
|
9/24/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency alarm in car is not working. Re-inspection required
|
4/25/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection)
|
x
|
|
Emergency light in car is not working on backup power. Re-inspection required
|
4/25/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Bottom hoistway access pull chain box is broken, repair or replace same
|
|