Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) A copy of the MCP shall be kept in the machine room for each elevator 5/22/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Bottom hoistway access pull chain box is broken, repair or replace same
MO Minimum : Elevators (I) - Pits (I)1 Clean the pit. 5/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency alarm in car is not working. Re-inspection required 4/25/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency light and bell are inoperative. Repair. 8/27/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light in car is not working on backup power. Re-inspection required 4/25/2025
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Fire fighters Phase I instruction sign at key switch is not legible. Replace sign 5/22/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Gate to machine space needs to be self locking 9/24/2024
MO Minimum : Elevators (A) - Hoistways (A)3 Hoistway doors at middle landing shall be adjusted to reduce gap between doors when closed and locked 5/22/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Pipes over elevator controllers and disconnect switches need to be guttered to prevent and possible leakage from getting into electrical equipment 9/24/2024
MO Minimum : Elevators (I) - Pits (I)1 Pit needs to be cleaned 9/24/2024
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)6 Post missing signs in car as needed. No pass., class freight. 5/19/2023
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)6 Provide Loading class" sign in car enclosure. 9/24/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Provide existing emergency lights and bell to work. 5/12/2023
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)1 Remove mounted fire extinguisher from inside the elevator. See ‘96 204.3a 5/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace missing controller cooling fan. 5/19/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Replace missing cotter pin on car door rod(s) as needed. 5/19/2023