A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
1001.2(c)(23)
|
|
|
Hoistway door safety access toggle switches shall be operable at all landings
|
5/22/2023
|
A17.1-1996 : Elevators
|
1.1 - Door Re-opening device
|
1001.2(a)(1)
|
|
|
Repair inoperable gate reversing edge on front car gate. Re-inspection required
|
5/22/2023
|
A17.1-1996 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
1206.2a (Pits and Hoistways)
|
|
|
Clean pit
|
7/5/2023
|
A17.1-1996 : Elevators
|
1.7 - Car door or gate
|
204.6
|
|
|
Front and rear gate off track. Repair
|
7/5/2023
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
1001.2(c)(23)
|
|
|
Hoistway door safety access toggle switches inopertive on all floors.
|
7/5/2023
|
A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7a (3)(a) Standby Illumination in the car. (Re-Inspection)
|
x
|
|
Emergency light and alarm inoperative on battery back-up.
|
6/9/2020
|
A17.1-1996 : Elevators
|
3.17 - Door and gate equipment
|
1001.2(c)(23)
|
|
|
Hoistway door safety access toggle switches inoperative on all floors.
|
7/5/2023
|
A17.1-1996 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in elevator machine room
|
5/22/2023
|
A17.1-1996 : Elevators
|
3.2 - Car top light and outlet
|
204.7
|
|
|
Light on cartop shall work, needs repaired
|
9/24/2024
|
conversion
|
conversion
|
n/a
|
|
|
Clean pit
|
7/5/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
|
|
Hoistway door safety access toggle switches shall be operable at all landings
|
9/24/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Need to repair inoperable gate reversing edge on front car gate. Re-inspection required
|
9/3/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
A copy of the MCP shall be kept in the machine room for each elevator
|
5/22/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
7/5/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace missing hoistway/car door/gate pull straps as needed.
|
7/5/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace missing cotter pin on car door rods (2).
|
7/5/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Replace missing hoistway doorlock interlock cover at 2nd floor.
|
7/5/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
|
|
Machine room lights were flickering during testing, repair as needed.
|
7/5/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit needs to be cleaned
|
9/24/2024
|