Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)5 No No Car ceiling panels are open egg crate type, providing no protection for passengers in event of bulb breakage. Panels should be replaced with solid panels or install plastic tubes and end caps over bulbs 6/2/2023
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Provide guard on bulbs in the elevator machine room. 5/18/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 5/18/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Provide current tested fire extinguisher in the elevator machine room. 5/18/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance No No Cylinder packing worn and leaking, repair as needed. 5/18/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Provide existing emergency lights to work. 5/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No Emergency light & alarm shall work in event of power outage. Re-inspection required 2/20/2023
MO Minimum : Elevators (F) - Electrical Switches (F)1 Yes No Cab stop switch inoperable. 10/12/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Phase I light and buzzer inoperative. Repair within 30 days. 10/12/2020
conversion conversion n/a No No Close space between cab gate sections. Left side. 4/22/2019