A17.1-1996 : Elevators
|
2.18 - Traction drive machines
|
208
|
|
|
Machine will not pick rated capacity due to load weight being out of calibration.
|
9/1/2019
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
|
|
Provide MCP
|
9/30/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Place current state operating certificate in elevator machine room
|
7/21/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevator malfunctioned before fire service could be tested. Test phase 1 and 2 fire service. Rule 8.6.4.19.6. Reinspect by 7-27-23 (30 days)
|
6/30/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Need to perform the following tests to complete the inspection: 125% brake, full load, full speed car buffer, full load, full speed car safeties. Re-inspection required
|
10/30/2024
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Unable to communicate with emergency personnel over phone. Re-inspection required
|
10/6/2022
|
A17.1-1996 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
202
|
x
|
|
Missing one lock nut on the bottom of the counterweight.
|
10/7/2020
|