Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.5.14.3(f) Yes No Test emergency power with inspector present 11/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.8 - Door closing force 2.13.4.2.3 Yes No FRONT DOOR TORQUE IS >30lbs 1/16/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.3 - Final and emergency terminal stopping devices 2.25.3 Yes Yes UP LIMIT NOT WORKING BEFORE WE HIT THE STOP RING 1/16/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No IN CAR EMERGENCY PHONE IS WORKING UNDER NORMAL CONDITIONS BUT NOT WORKING ON BATTERY BACK-UP 1/16/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures No No CAR DOOR DOES NOT STAY OPEN ON PHASE 2 FIRE SERVICE 1/16/2026
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1.1.5 Battery Backup Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No IN CAR PHONE IS WORKING UNDER NORMAL POWER CONDITIONS BUT NOT WORKING UNDER BATTERY BACKUP CONDITIONS
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.7 Firefighters' Emergency Operation: Operating Procedures No No CAR DOORS WILL NOT STAY OPEN DURING PHASE 2 FIRE SERVICE
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not operate 9/2/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 No No Provide means to disconnect car lighting in machine room. Existing disconnect has been bypassed. 2/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Provide "Elevator Emergency Power" signal in the lobby at the designated landing 9/8/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not operate without normal power 11/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 (Re-Inspection) Yes No Replace pit sprinkler head with sidewall sprinkler head located within 24 inches from pit floor 11/21/2023
MO Minimum : Elevators (H) - Machine Rooms (H)6 No No Label machine room equipment with identification that corresponds to identification inside the elevator and the car crosshead. 11/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates No No Identify inside of doors with a numeral corresponding to landing floor. Numeral to be a minimum of 4 inches tall. 11/16/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Test emergency standby operation with an inspector present. 8/23/2021