Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test emergency standby operation with an inspector present. 8/23/2021
MO Minimum : Elevators (H) - Machine Rooms (H)6 Label machine room equipment with identification that corresponds to identification inside the elevator and the car crosshead. 11/16/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 Provide means to disconnect car lighting in machine room. Existing disconnect has been bypassed. 2/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide "Elevator Emergency Power" signal in the lobby at the designated landing 9/8/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 (Re-Inspection) x Replace pit sprinkler head with sidewall sprinkler head located within 24 inches from pit floor 11/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 9/2/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Identify inside of doors with a numeral corresponding to landing floor. Numeral to be a minimum of 4 inches tall. 11/16/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate without normal power 11/21/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.5.14.3(f) x Test emergency power with inspector present 11/21/2023