Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 5/12/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x An in car emergency phone shall be provided. 11/18/2021
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x An in car emergency phone shall be provided. (Repeat Violation) 10/13/2020
A17.1-1996 : Elevators 2.4 - Machine space 1001.2(b)(4) Fire caulk hole in machine room wall. 5/12/2023
A17.1-1996 : Elevators 2.4 - Machine space 1001.2(b)(4) Fire caulk hole in machine room wall. (Repeat violation) 5/12/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Fire caulk hole in pit wall. 5/12/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Fire caulk hole in pit wall. (Repeat Violation) 5/12/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Fire caulk hole in the machine room wall. 5/12/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Fire caulk hole in the pit wall. 5/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Make the car top run button operational. 5/12/2023
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Properly guard the pit light. 5/12/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Properly guard the pit light. 5/12/2023
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Properly guard the pit light. (Repeat Violation) 5/12/2023
A17.1-1996 : Elevators 3.8 - Top emergency exit 1001.2(c)(12) Properly secure car top exit. 5/12/2023
A17.1-1996 : Elevators 3.8 - Top emergency exit 1001.2(c)(12) Properly secure car top exit. (Repeat Violation) 5/12/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 Properly secure the car top exit. 5/12/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Provide an emergency phone in the cab. 7/3/2019
A17.1-1996 : Elevators 1.7 - Car door or gate 1001.2(a)(7) Replace missing hoistway door sight guard at 4th floor. 5/12/2023
A17.1-1996 : Elevators 1.7 - Car door or gate 1001.2(a)(7) Replace missing hoistway door sight guard at 4th floor. 5/12/2023
MO Minimum : Elevators (S) - Fire Service (S)1 x Secure the smoke detector at top of hoistway. 7/3/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency lighting shall be operational. 11/18/2021
MO Minimum : Elevators (H) - Machine Rooms (H)4 The machine room shall be kept clean and all non-elevator related materials shall be removed from the machine room. 5/12/2023
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean. Clean the pit. 5/12/2023
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve on or before the next annual inspection. The valve shall be sealed and tagged after the category 5 test. 5/12/2023