MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
x
|
|
Restricted opening inoperative, repair.
|
9/30/2019
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
x
|
|
Repair car door restrictor.
|
1/30/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)12 (Door open zones)
|
x
|
|
Door restrictor works intermittently. Repair or replace.
|
10/1/2020
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
x
|
|
Existing pipes over the elevator equipment are leaking repair as needed.
|
7/31/2023
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
x
|
|
Existing pipes to be covered to prevent future leaks/condensation from the elevator equipment.
|
7/31/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
No audible signal on Phase I return.
|
1/30/2020
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Provide Phase I emergency recall operations by Fire Alarm Initiating Devices (FAID)
|
7/31/2023
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.7.1
|
x
|
|
Seal all machine room wall and ceiling penetrations.
|
7/31/2023
|
A17.1-2016 : Elevators
|
2.6 - Ventilation
|
2.7.9.2
|
x
|
|
Provide existing climate control in the elevator machine room to work properly.
|
7/31/2023
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Provide feeder location on main line disconnect (NEC620.51)
|
7/31/2023
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Provide feeder location on 110v. disconnect(NEC620.51).
|
7/31/2023
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.8
|
x
|
|
Provide pit GFCI outlet to work properly (NEC620).
|
7/31/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Provide pit bucket for oil collection.
|
9/17/2020
|