Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.36 - Hydraulic Cylinders 8.6.5.5.2 Collection of Oil Leakage Oil leakage collected from each cylinder head seals or packing gland shall not exceed 5 gal before removal. 2/10/2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light shall work 3/25/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.1 Examination and Maintenance Packing on hydraulic cylinder is leaking excessively, needs to be replaced 3/25/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 3/25/2024