Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State certificate in machine room 8/8/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 8/8/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State certificate in machine room 8/8/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2 Design and Construction of Pits No No Repair pit lights 8/8/2022
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) Yes No OSV is not sealed, perform required testing, seal & tag within 90 days or before 7/19/22. Re-inspection required 7/6/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency communication inoperable, no voltage on phone line, needs repaired. Re-inspection required
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service testing and document on log in machine room 8/8/2022
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Perform monthly fire service test & document on log in machine room 8/8/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Repair pit light 8/8/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light is not working 8/8/2022
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light does not work and shall function. Repair or replace 7/20/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door shall be self locking. Remove material from door jamb preventing door from locking 8/8/2022
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Machine room shall not be used for storage. Remove all non elevator related items 8/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No A written copy of the MCP shall be kept in the machine room for each elevator 8/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher in machine room is expired, needs to be replaced or have serviced 8/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide complete control program and palce on controller in machine room 8/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean cartop 8/8/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Patch ceiling in machine room to maintain fire rating 8/8/2022