Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)1 Alarm Bell not working 9/10/2018
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)2 Emergency phone not working Reinspection needed 9/10/2018
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an overspeed valve that is not sealed. It shall be tested with the rated load on or before the next annual test per the MO AHJ.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car emergency lights shall be operational. 4/14/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The in car alarm bell shall be operational on auxiliary power. 4/14/2023
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Firefighters operation shall be tested as required by CSR 40-5.090(3)(A) 12/30/2020