MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Firefighters operation shall be tested as required by CSR 40-5.090(3)(A).
|
12/30/2020
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Emergency power operation of the elevator shall be tested. All units in Building D are due for this testing.
|
3/1/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 Maintenance, Repair and Replacements
|
|
|
Replace leaking jack packing
|
4/10/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove oil from pit floor
|
4/10/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
12/21/2023
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.14.2 Hydraulic Cylinders and Pressure Piping
|
x
|
x
|
Oil leakage during 15 minute standing test. Take corrective action as needed and perform 15 minute standing test again. Unit is down for repair but not red tagged. Violation still needs to be cleared as of 3/1/2024.
|
|
A17.1-2016 : Elevators
|
2.36 - Hydraulic Cylinders
|
8.6.5.14.2 Hydraulic Cylinders and Pressure Piping
|
x
|
x
|
Oil leakage during 15 minute standing test. Take corrective action as needed and perform 15 minute standing test again. Unit is down for repair but not red tagged.
|
3/1/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an overspeed valve that is unsealed. A category 5 test shall be performed on or before the next annual inspection. The valve shall be tagged and sealed after the category 5 test.
|
12/30/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
The overspeed valve is not sealed. It shall be tested with the rated load in 2022.
|
12/30/2022
|