Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service (S)1 x Complete annual inspection- test fire service 5/28/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x The counterweight governor rope has multiple breaks. Elevator Red Tagged. 8/11/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The following testing items remain and must be completed: The car and counterweight safeties shall be set, the car and counterweight buffer shall be tested, and the 125% brake test. 8/11/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The following testing items remain and must be completed: The car and counterweight safeties shall be set, the car and counterweight buffer shall be tested, and the 125% brake test. 9/7/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power operating of the elevator shall be tested annually. Testing is due. 3/1/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x x The counterweight governor pull-through was inadequate to operate the safeties. The governor shall be repaired or replaced so that the governor pull-through force is at least 67% greater than the force required to activate the safety. Note: The elevator has been locked and tagged out of service by Schindler Elevator. A re-inspection is required before the unit can return to service. Elevator Red Tagged. 8/22/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The annual test needs to be performed in it's entirety. None of the test was witnessed today due to issues with the unit. 8/22/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 12/21/2023