Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. Dials, answered, operator can hear us, but we cannot understand her (intermittent speaker). 7/31/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 12/28/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. Dials, answered, operator can hear us, but we cannot understand her (intermittent speaker). Violation not cleared as of 7/31/2024.
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean. Remove excess debris.
MO Minimum : Elevators (I) - Pits (I)1 Clean the pit of dirt and debris. 12/28/2022
MO Minimum : Elevators (I) - Pits (I)1 Pits shall not be used for storage purposes. There are two large extension ladders being stored in the pit.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) The suspension ropes shall be tagged as specified by CSR 40-5.065(L)1. A tag was not provided for the new ropes.
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Ropes are undersized and have excessive rouging. 3/1/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Ropes are undersized and have excessive rouging. (Violation still not corrected/re-inspected as on 3/1/24) 7/3/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Ropes are undersized and have excessive rouging. This violation has been cited 2 times prior and has not been fixed. Third and final reinspection within 15 days (7/18/24), if not compliant, unit must be red-tagged and removed from service. 7/31/2024
MO Minimum : Elevators (S) - Fire Service (S)1 x Complete annual insption-test fire service 5/28/2019
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Car would not operate on emergency power. Emergency operation of the elevator shall function and be tested. 10/14/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Emergency power operation of the elevator shall be tested. All units in Building D are due for this testing. 3/1/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.