Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.32 - Control Valve 8.11.3.1.2(t) x x 8.6.5.14.2 The victaulic fitting underneath the control valve in the hydraulic tank is leaking excessively with failure being imminent. Repair or replace fitting. Unit is placed out of service and a reinspection is required before the elevator can be returned to service. 9/3/2025