Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 9/30/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone does not operate 11/21/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Identify inside of hoistway doors with a numeral corresponding to landing floor. 11/16/2021
MO Minimum : Elevators (H) - Machine Rooms (H)6 Label machine room equipment with identification that corresponds to identification inside the elevator and the car crosshead. 11/16/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Perform emergency standby operation with an inspector present. 8/24/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x Provide "Elevator Emergency Power" signal at the lobby of the designated landing. 9/8/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Provide lighting in machine room. Existing feed for machine lights has no electrical power 2/22/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 Illumination of Pits REPAIR PIT LIGHTING 10/21/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 (Re-Inspection) x Replace pit sprinkler head with sidewall sprinkler head located within 24 inches of pit floor 11/21/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.5.14.3(f) x Test emergency power operation with inspector present 11/21/2023