Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) x Provide minimum c/w run by. 8/2/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)2 Wire ropes are degraded beyond specifications and need to be replaced. Reinspection required within 60 days. 9/11/2019
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Diameter loss due to rouging exceeds proposed criteria suspension means. 5/6/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.15 - sign and operating device symbols 2.26.12 x A sign shall be posted adjacent to the hall call fixtures at each floor instructing occupants not to use the elevator in case of a fire. The sign shall include only the wording and graphics shown in Fig. 2.27.9 of A17.1-2005. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 x A standby power test shall be performed. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 2.26.4 x The main disconnects shall have feeder locations labeled. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.11 - Disconnecting Means and Control 2.26.4 x The car lighting branch circuit shall be separate and shall not feed the hall button riser power supply. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 x The machine room light bulbs shall be guarded. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 8.11.2.1.2(c) x Provide at least one GFCI duplex receptacle in the machine room. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.4 - Machine space 2.7.2.1 x Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.11.2.1.2(g) x Provide a current ABC type fire extinguisher in the machine room. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 x Machine room wiring shall be enclosed. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 x All wireway and electrical device covers shall be installed. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 x Temporary wiring shall be removed. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.20 - Governor rope 2.18.5 x A governor rope tag shall be installed. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 4.8 - Hoistway enclosure 2.1.1 x The penetrations in the hoistway shall be sealed. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump pump shall be provided x 2.2.2.6 - The sump pump cover shall be level with the pit floor. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.1 x 2.4.5 - A counterweight runby sign shall be installed in the pit. 10/9/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Expired 2/15/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.