MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
Provide minimum c/w run by.
|
8/2/2022
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)2
|
|
|
Wire ropes are degraded beyond specifications and need to be replaced. Reinspection required within 60 days.
|
9/11/2019
|
MO Minimum : Elevators
|
(L) - Wire Ropes-Hoisting, Governor and Tiller
|
(L)12 (Re- Inspection)
|
x
|
|
Diameter loss due to rouging exceeds proposed criteria suspension means.
|
5/6/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.15 - sign and operating device symbols
|
2.26.12
|
x
|
|
A sign shall be posted adjacent to the hall call fixtures at each floor instructing occupants not to use the elevator in case of a fire. The sign shall include only the wording and graphics shown in Fig. 2.27.9 of A17.1-2005.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
A standby power test shall be performed.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
2.26.4
|
x
|
|
The main disconnects shall have feeder locations labeled.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4
|
x
|
|
The car lighting branch circuit shall be separate and shall not feed the hall button riser power supply.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1
|
x
|
|
The machine room light bulbs shall be guarded.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
8.11.2.1.2(c)
|
x
|
|
Provide at least one GFCI duplex receptacle in the machine room.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.4 - Machine space
|
2.7.2.1
|
x
|
|
Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.2.1.2(g)
|
x
|
|
Provide a current ABC type fire extinguisher in the machine room.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
x
|
|
Machine room wiring shall be enclosed.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
x
|
|
All wireway and electrical device covers shall be installed.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
x
|
|
Temporary wiring shall be removed.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.20 - Governor rope
|
2.18.5
|
x
|
|
A governor rope tag shall be installed.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
4.8 - Hoistway enclosure
|
2.1.1
|
x
|
|
The penetrations in the hoistway shall be sealed.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump pump shall be provided
|
x
|
|
2.2.2.6 - The sump pump cover shall be level with the pit floor.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.1
|
x
|
|
2.4.5 - A counterweight runby sign shall be installed in the pit.
|
10/9/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Expired
|
2/15/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|