Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Yes No All wireway and electrical devices covers shall be installed. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.1 Yes No Temporary wiring shall be removed. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.10 - Hoistway construction 2.1 Yes No The penetrations in the hoistway shall be sealed with approved solid material. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.2 - Bottom clearance, runby, and minimum refuge space 2.4.5 Counterweight Runby Data Plate Yes No A counterweight runby sign shall be provided in the pit. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.17 - Standby power operation 2.27.2 Yes No A standby power test shall be performed. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.2-2.27.8 Yes Yes The new smoke installation shall be completed and tested. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Yes No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The in car emergency telephone shall be operational. 10/9/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.10 - Numbering of elevators, machines, and disconnect switches 2.29.1 Yes No An identification number or letter shall be provided adjacent to or on every elevator entrance at the designated level, and be a minimum of 3 inches in height. 10/9/2020
conversion conversion n/a No No Repair gaps on car doors over 3/8" wide 1/29/2026
conversion conversion conversion - reinspect Yes No Cab emergency lights do not work. 3/22/2019
conversion conversion n/a No No Traction machine worm seal leaking oil 1/29/2026
MO Minimum : Elevators (G)2-Alterations 8.7.2.14.2 Car Enclosure Yes No Emergency alarm bell and light shall work. 9/4/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.11 Runby (Re-Inspection) Yes No Provide minimum c/w run by. 8/2/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Expired 1/29/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 1/29/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.2.5 Rope Tension (Re-Inspect) Yes No The rope shall be shortend. Unit was red tagged.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Inspection incomplete. 100% set, unintended motion, and 125% run/hold remain to be tested.