ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
The penetrations in the hoistway shall be sealed with approved solid material.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone shall be operational.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
A standby power test shall be performed.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.2-2.27.8
|
x
|
x
|
The new smoke installation shall be completed and tested.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
2.29.1
|
x
|
|
An identification number or letter shall be provided adjacent to or on every elevator entrance at the designated level, and be a minimum of 3 inches in height.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.5 Counterweight Runby Data Plate
|
x
|
|
A counterweight runby sign shall be provided in the pit.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
x
|
|
All wireway and electrical devices covers shall be installed.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.1
|
x
|
|
Temporary wiring shall be removed.
|
10/9/2020
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
x
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
10/9/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Expired
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.4.11 Runby (Re-Inspection)
|
x
|
|
Provide minimum c/w run by.
|
8/2/2022
|
MO Minimum : Elevators
|
(G)2-Alterations
|
8.7.2.14.2 Car Enclosure
|
x
|
|
Emergency alarm bell and light shall work.
|
9/4/2020
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Cab emergency lights do not work.
|
3/22/2019
|
conversion
|
conversion
|
n/a
|
|
|
Traction machine worm seal leaking oil
|
|
conversion
|
conversion
|
n/a
|
|
|
Repair gaps on car doors over 3/8" wide
|
|