Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits No No Pit must be free of water. (currently 2" standing water in pit) 10/16/2024
conversion conversion n/a No No needs smoke detector at first floor, heat detector in machine room needs to be smoke detector all need tested when replaced 11/8/2018
conversion conversion n/a No No air conditioner not cooling in machine room needs replaced or repaired 11/8/2018
conversion conversion n/a No No no current certificate posted 11/8/2018
conversion conversion n/a No No water in pit sump not working 11/8/2018
conversion conversion conversion - reinspect Yes No Telephone line dead--REINSPECT REQUIRED 7/11/2018
MO Minimum : Elevators (I) - Pits (I)1 No No I-1 water in pit sump not working 40-5.100 needs current certificate posted in machine room 4/30/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No needs current certificate posted 4/30/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No 1.5 energency light needsa battery 9/30/2020
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No needs smoke detector first and secomd floor landings and the heat detector in the machine room needs to be a smoke detector 9/30/2020
MO Minimum : Elevators (I) - Pits (I)1 No No the pit needs to be dry and clean 4/30/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Unauthorized material 4/30/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Remove oil scavenger pump 4/30/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No car riding lantern missing cover/lamps 4/30/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency Light/Bell failed 5/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams No No No wiring diagrams 4/30/2021