Missouri Minimum : Escalators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) display of certificate
|
|
|
A current state operating certificate shall be obtained and displayed. Note: The displayed certificate expired 7/1/18.
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
(T)2(B)
|
|
|
Lower start switch needs to be replaced.
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.8.3 Step/Skirt Performance Index
|
x
|
|
Need compliant step/skirt performance index test performed.
|
|
conversion
|
conversion
|
n/a
|
|
|
Replace lower landing keyed start switch. Will not return to center position.
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.11.5.2(i) Demarcation lighting
|
x
|
|
Upper and lower demarcation lighting inoperative.
|
9/7/2021
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.11.5.2(i) Demarcation lighting
|
x
|
|
Upper and lower demarcation lights not working
|
12/7/2021
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Upper and lower walk-on deck switches are taped/defeated. Repair/adjust.
|
|