conversion
|
conversion
|
n/a
|
|
|
Replace broken step tread
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
(T)2(E)
|
|
|
Replace broken comb plates where needed.
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
(T)2(E)
|
|
|
Replace broken step treads where needed.
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
(T)2(G)
|
|
|
Perform step/skirt index when construction is finished.
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
(T)2(F)
|
|
|
Need to straighten lower deck plate.
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.8.13 Escalator Cleaning
|
|
|
Clean pits
|
|
Missouri Minimum : Escalators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) display of certificate
|
|
|
A current MO State operating certificate shall be posted near the equipment, in a noncombustible frame with a clear protective vision plate over it. Note: Certificate expired 7/1/2018.
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Upper and lower walk-on deck switches are taped/defeated. Repair/adjust.
|
|
Missouri Minimum : Escalators
|
(T) - Existing Dumbwaiters, Escalators and Moving Walks
|
8.6.11.5.2(i) Demarcation lighting
|
x
|
|
Upper demarcation light no working
|
12/7/2021
|